CC_a003 — CCID Tripped

Full alert identifier: CC_a003_CCIDTripped

Message shown in the car

Unable to charge - Wall Connector GFCI tripped Disconnect and retry or use different equipment

Alert description

Ground fault current exceeded threshold.

Potential impact

Wall connector will not allow charging until ground fault current path is corrected and the test rerun.

Set condition

Ground fault current exceeded threshold.

Clear condition

Ground fault current has been corrected, and the test rerun. Test reruns after 15 minutes (non-EU), cable cycle, or reset button.

Signals to check

Open this alert in Service Mode Plus and review the Payload tab. Use the field names below to identify the values shown by your vehicle.

Signal Unit
Dc Gfci Current CC_a003_dcGfciCurrent A
Gfci Rms Current CC_a003_gfciRmsCurrent A
Gfci Rms Current Avg CC_a003_gfciRmsCurrentAvg A
Signal Unit
Gfci Fault Bucket CC_a003_gfciFaultBucket —
Gfci Fault Reason CC_a003_gfciFaultReason
0
SNA
1
AC LPF
2
AC PEAK
3
DC LPF
4
DC PEAK
—

Check other alerts

With Service Mode Plus enabled, open Service Alerts → All. Review the other alerts for clues to the cause of CC_a003.