VCDOORRL_a121 — eFuse Management Continuous16 V

Full alert identifier: VCDOORRL_a121_eFuseManagementContinuous16V

Alert description

Unexpected voltage seen on continuous device outputs

Potential impact

Electrical loads for door switch LED, door pocket LED, door puddle LED, and power 15v0 sw fused rail may be unavailable.

Set condition

Voltage is above 10V for 200ms on at least one of the device outputs while none of them are being driven

Clear condition

Voltage is below 10V and 10 seconds have passed since alert was set. If the alert sets 3 or more times, controller reset is required.

Signals to check

These diagnostic fields are associated with VCDOORRL_a121. Check the alert's Alert Log in Service Mode Plus for available values.

Signal Unit
Continuous 16 VE Fuse Monitor VCDOORRL_a121_continuous16VEFuseMonitor V
E Fuse Trip Count VCDOORRL_a121_eFuseTripCount —

Check other alerts

With Service Mode Plus enabled, open Service Alerts → All. Review the other alerts for clues to the cause of VCDOORRL_a121.