CC_a001 — Gnd Mon Intrpt Line Side
Full alert identifier: CC_a001_gndMonIntrptLineSide
Alert description
Wall connector protective earth is disconnected or grounding scheme dual in-line package (DIP) switch is set incorrectly.
Potential impact
Wall connector will not allow charging until the protective earth connection is corrected.
Set condition
Wall connector alternating current (AC) input side ground impedance is above threshold.
Clear condition
Wall connector AC input side ground impedance has fallen below threshold for adequate time.
Signals to check
These diagnostic fields are associated with CC_a001. Check the alert's Alert Log in Service Mode Plus for available values.
| Signal | Unit |
|---|---|
Ground Resistance
CC_
|
Ohm |
Check other alerts
With Service Mode Plus enabled, open Service Alerts → All. Review the other alerts for clues to the cause of CC_a001.